ATEX / IECEx II 2 G Ex d IIC T6 Gb Zone 1 & 2, IP66 ( NEMA 4) CU TR (formerly GOST)
The flameproof „HFT“ thermostat is ATEX certified and suitable for installation in zone 1 and 2 hazardous areas.
It is designed for the temperature control of hazardous area air heater.
Features for thermostat type HFT:
- Wall mounted
- Cast Stainless steel enclosure certified weatherproof to IP66
- Suitable for ambient temperatures -60°C to +60°C
Technical information for thermostat type HFT:
Certification
- ATEX / IECEx II 2 G
- Ex d IIC T6 Gb Zone 1 & 2, IP66 ( NEMA 4)
- CU TR (ehemals GOST)
Enclosure
Cast stainless steel with two M20 cable entries (plugged), external and internal earths and internal neutral link
Controls
Choice of control range :
- HFT 40 – internal scale 0…4 – control range 0….+40°C
- HFT 60 – internal scale 0…6 – control range 0….+60°C
- Hysteresis 5-10 K
Mounting
2x6mm diam. shrouded mounting holes are provided